PV POWER FOR FIVE RAILWAY LEVEL CROSSINGS

Objectif

PV power for signals and gate arms of five level crossings of a railway. For safety reasons high reliability of the power supply is required.

Five level crossings of the secondary railway line from Pisa to Vada, between Pisa and Collesalvetti are equipped with standard (FFSS), type V301, automatic gates and signals.
The subsystem "Ospedaletto" (closer to Pisa) powers two level crossing the nearby subsystem "Casa del Vento" (closer to Collesalvetti) powers three level crossings.
Nr. subsystems : 2
Power subsys. : 2 x 6800 Wp
Total power : 13.6 kWp
Backup : mobile generator set for fast recharge of batteries
Nr. of modules : 144 for each system (of which 8 short-circuited)
Module descrip. : ITALSOLAR (now EUROSOLARE), Type 36 MS/C, 50 Wp, monocristalline. 36 cells, 5 inch square, 960 x 443 x 35 mm, 7.5 kg.
Connection : Four strings of 10 series connected panels (120 V operation, 220 V open circuit) in the subarray which is directly and continuously connected to the battery. Two other subarrays with four strings of 12 series connected modules are connected through the charge regulator.
Support : on special structures, 57 deg. tilted
Max. pwr. trcker : none
Chrg.controler : Special multiple stage regulator.
Battery : FIAMM. Type SMBF/7, lead-acid.
Batt. (V) : 144
Batt. (Ah) : 867 Ah (for each system)
Batt. (kWh) : 124 kWh (for each system)
Inverter : Special design; Two in parallel for increased reliability.
Inv. in (V) : 144 V
Inv. out (V) : 150 V, 50 Hz
Inv. power (kW) : 600 VA
Load descrpt. : 144 V, DC for the motors of the gate arms. The signal lights and all of the safety system are powered (through the inverter) by 150 V AC. Average energy drain: 10 to 16 kWh per day.
Monitoring: At the "Ospedaletto" subsystem irradiance (Kipp & Zonen), temperature, currents, voltages, ecc. (about 16 data) are measured and stored as hourly averages on the hard disk of a personal computer. The data are collected every two month on a floppy disk for further processing. The "Casa del Vento" subsystem is not monitored.

Appel à propositions

Data not available

Régime de financement

DEM - Demonstration contracts

Coordinateur

Sistemi Energetici Integrati
Contribution de l’UE
Aucune donnée
Adresse
VIA SAN JACOPO 32
50047 PRATO
Italie

Voir sur la carte

Coût total
Aucune donnée