{"contenttype":"result","language":"en","availableLanguages":"en","rcn":"169311","id":"256766_PS","title":"Final Report Summary - FITUP (Fuel cell field test demonstration of economic and environmental viability for portable generators, backup and UPS power system applications)","teaser":"Executive Summary:19 market-ready fuel cell systems from two suppliers (Electro Power Systems and Future-E) have been produced and installed as UPS (Uninterruptible Power Supply) backup power sources in selected sites across Europe (Italy, Switzerland, and Turkey). Real-world...","summary":"Executive Summary:\n19 market-ready fuel cell systems from two suppliers (Electro Power Systems and Future-E) have been produced and installed as UPS (Uninterruptible Power Supply) backup power sources in selected sites across Europe (Italy, Switzerland, and Turkey). Real-world customers from the telecommunications industry (Swisscom,  Polycom, Wind and Turkcell) used thirteen fuel cell-based systems, with power levels in the 3-12 kW range, in their sites. On the other hand benchmark tests of six fuel cell UPS systems have been implemented at the research centres (JRC, Environment Park, LUASA, IBU) to validate the lifetime of the systems. \nGrid failures are imposed in these sites according to the test protocol developed for each application. Test protocol provides a tool to check whether the systems satisfy end-user backup power requirements at different levels of grid quality. Three distinct goals of the project has been focused in the test results and compared:\n\u2022\tReliability greater than 95%\n\u2022\tResponse time less than 5 ms\n\u2022\t1500 hours and 1000 cycles of system lifetime in benchmark tests and no considerable performance deterioration for the on-field systems.\nCombining all the tests in the project, a total of 10,397 cycles have been tested. Systems responded to 10,332 of these cycles successfully to provide 6,573 hours of backup power without interruption. The average reliability of all systems tested in the project reaches 99.4% which is well above the project goals. Individual system reliability has differed from 97% to 100%, which assures each of tested systems has surpassed the projected goals individually. The total energy production during the tests has surpassed 18.7 MWh with an average power output of 2.85 kW for the 17 systems tested. Long term durability tests prove that expected lifetime has been reached both in terms of cycles and operating hours. Finally all the systems are proven to provide the same rated power at the end of the tests, which hints that there is not a considerable deterioration in the system performance.\nThus technical viability and reliability of back-up fuel cell systems have been proven on the field.\nA lifecycle analysis using data from the project has been carried out by UNITOV to determine economic and environmental value proposition over incumbent technologies such as batteries and\/or diesel generators, including a TCO analysis as comparison criteria.  The comparison of competing technologies in three different scenarios confirms that the FC backup system is an environmental friendly solution. \nUsing the expert advice of T\u00dcV S\u00fcd the project also studied a proposal for a uniform certification procedure for Fuel Cell Systems as backup and UPS power systems.\n\nThe dissemination of project progress has been geared mostly towards getting the word out to final users through presentations at specialised conferences, thus improving the visibility of market-ready fuel cells and pave the way for market penetration. \n\nNon-technical barriers, i.e. all those barriers to deployment that are not specific to the technical performance of the products demonstrated, for the exploitation of fuel cell systems for back-up power \/ UPS applications and recommendations regarding the removal or reduction of these non-technical barriers to deployment have been identified.\nProject website: http:\/\/fitup.engr.bilgi.edu.tr\/\nProject coordinator: Ilaria Rosso, Electro Power Systems S.p.A. ilaria.rosso@electropowersystems.com.\n\nProject Context and Objectives:\nFuel cells are electrochemical devices that convert chemical energy in fuels into electrical energy directly, with high efficiency and low environmental impact. There is a wide range of potential applications for fuel cells including transportation, on-site residential power generation, auxiliary power systems and material handling. Figure 1 show the total number of units installed worldwide for different application areas.\nFuel cells are very promising technology for automotive applications when concerned with high range and fast refuelling requirements of the alternative technology replacing internal combustion engines. On the other hand, the commercialization of fuel cell vehicles can take up some more time due to lack of fuelling infrastructure and high costs associated with the very small scale of manufacturing. However, even with the current state of the technology, fuel cells have become commercially viable solutions for some applications such as material handling and backup power. This is mainly due to the attenuated operating costs of fuel cell systems when compared to competing battery and fossil-fuel technologies.\nBackup power technologies currently include batteries and generators operating on diesel, propane, or gasoline where the former has advantages of zero emissions operation standing out for indoor applications. Fuel cells also being emissions free become another alternative when environmental impacts are concerned. Moreover, compared to batteries, fuel cells offer longer continuous runtime and greater durability in harsh outdoor environments under a wide range of temperature conditions. With fewer moving parts, they require less maintenance than both generators and batteries.\nAlso lifetime of the fuel cell systems is higher than battery systems, significantly reducing the maintenance costs associated with replacement batteries.\nSeveral studies have pointed out the economic benefits of fuel cells over these other , . In a study for the U.S. Department of Energy, Battelle Memorial Institute analysed lifecycle costs of emergency response radio towers, comparing fuel cells with a 2 kW battery-only backup (8 hours autonomy) and a 5 kW battery-diesel generator backup (52 hours, 72 hours, and 176 hours backup duration). PEM fuel cells can provide service at substantially lower total cost than current technologies (the higher cost for the fuel cell system for the 176-hour backup results from the cost of hydrogen storage tank rental).\nSales and installations of backup power systems in the US have been increased recently with the federal grants and tax incentives. Latest reports show that there have been 5023 fuel cell backup power units deployed in the US . 907 of these systems are government funded which presumably led to 4116 industry funded installations. Industry installations itself jumped from 3593 to 4116, about 15% in the last one year. Total amount of government funding for these systems are reported to be $18.5 million. These funding are utilized in the sites of US telecom operators such as AT\u0026T, Sprint, utilities company PG\u0026E and military sites of Warner Robins Air Force Base and Fort Irwin. These kind of incentives definitely has helped fuel cell industry in the US with companies like ReliOn Inc reporting more than 3.9 MW of installed capacity in more than 1350 customer sites, Altergy Systems reaching more than 5 million hours of operation in the telecommunications applications  and stack manufacturer Plug Power deploying more than 4500 stacks for various applications accumulating over 20 million hours of runtime .\nDeveloping countries also increasingly used fuel cells for back-up and remote power. Wireless TT Info Services in India purchasing 200 Plug Power systems.  IdaTech continued its focus on Indonesia, receiving an order for 154 ElectraGen\u2122 H2 fuel cell systems, adding to the more than 100 IdaTech fuel cell systems already installed across Indonesia for telecommunications backup power . In 2012, Idea Celullar of India ordered 30 systems from Ballard following the regulations of the Indian government which required 50% of the rural base stations and 33% of the urban ones using hybrid power sources including fuel cells . Indonesian company Cascadiant ordered 102 Ballard systems to be used in their networks reaching 500 units cumulative. Moreover, Ballard reported shipment of 300 units to Inala Technologies in S. Africa, 350 units to NSN in Japan and 170 units to Azure Hydrogen in China . \nIn the EU, the manufacturers have made inroads into the marketplace, but could still greatly benefit from a project such as FITUP. So far, the level of sales in EU countries by EU suppliers appears to have been somewhat limited, although they have been increasing. The fuel cell suppliers participating in the FITUP project are ramping up production of their units. At the same time, widespread knowledge of this technology is still an objective to be achieved in order for potential users from a number of industries to consider using fuel cells, alongside batteries or diesel generators.\n\nBecause the number of demonstrations of fuel cell-based backup power applications has been limited, there is a lack of data for users to access. Without references, many potential users are understandably reticent to try a new technology that provides reliability for their networks, e.g. in the case of the telecommunications industry. Furthermore, the set of criteria for commercialization that are included in the call regarding reliability, durability, cost, cyclability and response times, have not, as a whole, been proven with a representative set of units.\n\nFITUP project\u2019s aim is to overcome these problems, carrying on an extensive test campaign that will supply data about the systems and spread technology knowledge.\n\nIn the FITUP project a total of 19 market-ready fuel cell systems from two suppliers, Electro Power Systems and Future-E, have been installed as backup power sources in selected sites across Europe. Customers from the telecommunications industry and public safety departments in Italy, Switzerland and Turkey tested these fuel cell-based systems in real life conditions, with power levels in the 3-12 kW range. \nThe goal of the project is to demonstrate a level of technical performance (start-up time, reliability, durability, number of cycles) that qualifies them for market entry, thereby accelerating the commercialization of this technology in Europe and elsewhere.\n\nFITUP project has involved testing systems from both fuel cell suppliers at real life-conditions and laboratory benchmarking tests according to a test protocol developed in the scope of the project. The performance and availability data have been logged and analysed to draw conclusions regarding commercial viability and degree to which they meet customer requirements, as well as suggesting areas for improvement.\n\nAlso, a lifecycle analysis using data from the project have been carried out to determine economic and environmental value proposition over incumbent technologies such as batteries or diesel generators.\n\nThe system producers used the results of the tests to obtain valuable first hand feedback from customers and optimized their systems as needed in the course of the project. On the other hand, final users participated in the project have had the chance for first-hand experience of the use of fuel cells to be used in their applications.\n\nAnother goal of the project is to develop a certification procedure, under the supervision of T\u00dcV S\u00fcd, valid in the countries of the project where either the fuel cells systems are produced or tested. Moreover, the dissemination of project is aimed towards improving the industry awareness of the fuel cell systems and pave the way for market penetration.\n\nIdentification of non-technical barriers, i.e. all those barriers to deployment that are not specific to the technical performance of the products demonstrated, for the exploitation of fuel cell systems for back-up power \/ UPS applications represents a further objective of the project.\n\nThe consortium consists of large and small entities, which are fuel cell suppliers, end users and R\u0026D centres (for data acquisition and analysis). The list of partners is given in Table 1. The partners are located throughout Europe covering a range of environmental conditions, such as those found in Italy, Switzerland and Turkey. \nTable 1: List of partners\n\nPartner Name\tCountry\tRole in the project\tContact name \n\nElectro Power Systems\tItaly\tFuel cell manufacturer\tIlaria Rosso\nilaria.rosso@electropowersystems.com\nFutureE Fuel Cell Solutions\tGermany\tFuel cell manufacturer\tMark-Uwe Osswald \nmark-uwe.osswald@future-e.com\nEnvironment Park\tItaly\tR\u0026D centre\tAlessandro Graizzaro\nalessandro.graizzaro@envipark.com\nLucerne University of Applied Sciences and Arts\tSwitzerland\tR\u0026D centre\tUlrike Trachte\nulrike.trachte@hslu.ch\nUNIDO-ICHET (Terminated on 31st  December 2012)\tTurkey\tR\u0026D centre\tn.a.\nJoint Research Centre\tNetherlands\tR\u0026D centre\tThomas Molkow\nthomas.malkow@ec.europa.eu\nT\u00dcV S\u00dcD Industrie Service GmbH\tGermany\tCertification body\tTim Faber\ntim.faber@tuev-sued.de\nSwisscom (Schweiz) AG\tSwitzerland\tEnd user\tWilly Kolher\nwilly.kohler@swisscom.com\nWind\tItaly\tEnd user\tReale Aniello\naniello.reale@Mail.Wind.it\nBetriebskommission Polycom Nidwalden (BKPNW)\tSwitzerland\tEnd user\tHans Buchel\nhans.buechel@kfnmail.ch\nUniversit\u00e0 di Roma Tor Vergata\tItaly\tR\u0026D centre\tStefano Cordiner\ncordiner@uniroma2.it\nIstanbul Bilgi University\tTurkey\tR\u0026D centre\tFazil Mustafa Serican\nfazil.serincan@bilgi.edu.tr\n\n\n\nProject Results:\nThe strategy of the work plan of the FITUP project is laid out in three separate major steps. First, the systems were produced and installed prior to testing the systems, second, testing of all systems took place at sites selected by final users, third, the data from the field tests have been gathered and evaluated; conclusions on lessons learned, suggestions for improvement and a full lifecycle analysis have been carried out enabling assessment of environmental, technical and economic feasibility of the use of this technology. The list of the work packages is given in Table 1.\n\nDuring the first phase, before the systems are tested, a number of steps were taken. These include: \n\u2022\tProduce and install fuel cell systems \n\u2022\tInstall hydrogen infrastructure that meet applicable legislation and customer requirements\n\u2022\tDetermine and install testing equipment and monitoring protocol to be implemented \n\u2022\tDevelop test architecture and protocol\nFollowing the development of the test protocol and installations of the systems, the testing phase started and continued throughout the rest of the project. This phase comprises benchmarking procedures as well as field demonstrations. The benchmarking activities provide a reference against which the results from field trials can be compared.\nTesting activities have been accompanied and supported with the data analysis in WP5. Testing algorithms are indeed modified in order to efficiently deal with the collected data. In this work package the collected data will be interpreted to assess the fuel cell systems within the scope of project outcomes.\nThere are three other tasks that are ancillary, yet vitally important to the success of the project. WP\u2019s 1, 6 and 7 complement the work outlined. WP1 deals with management and coordination. In WP6 a certification procedure suitable for these systems across the EU will be proposed. In WP7 dissemination activities will be carried out, including website management and organisation and attendance at seminars or workshops and identification of non-technical barriers.\nMain S\u0026T results and foregrounds are therefore related to WP2, WP3, WP4 and WP5.  \n1. WP2 \u2013 Production of the Fuel Cell Systems\nFor this work package, the two manufacturers, ElectroPS and FutureE, lead their own work. ICHET acted as WP leader, given its status as independent party and oversee the work being undertaken by both suppliers. \nWithin this WP two tasks have been identified and executed:\nTask 2.1: Production of fuel cell systems for benchmark by research centres and for installation in the field at end user sites\nStarting from month 1 of project activities the fuel cell systems have been produced by the two manufacturers and shipped to the research centres and final users.\nEach supplier will produce 3 fuel cell systems for benchmarking, while the rest will go towards field demonstrations. The systems from both suppliers will be mounted in a cabinet and can be remotely monitored. This remote monitoring capability will be integrated with the data acquisition and analysis equipment provided by the R\u0026D centres in charge of monitoring. Their respective products are deemed ready for commercialisation and therefore are suitable for demonstration under the scope of this project. \nDepending on the detailed site specific requirements and the installation procedures of the selected operators, the power level, the power type (DC\/AC) and the configuration (indoor\/outdoor) can vary. By using portable 19\u201d rack mounts, the fuel cell systems are designed to allow for custom specific variations while maintaining a high level of standardized components. For the FITUP project this meant that the manufacturers were able to change the hardware from site to site at least in some details but that the overall fuel cell power system remained a standard module. Regardless of the customization it was possible to apply standard manufacturing and test procedures and it will be possible to generate statistically relevant test data that can be compared with each other due to the similarity of the core of the systems. \nFuel cell systems produced for benchmark tests are listed in the table 2 with related date of shipment:\n\nSome changes in the final user sites definition, power outputs and technical specification requests with respect to what had been foreseen at the time of the proposal presentation occurred and brought about some delay in the completion of production and delivery of the systems for final users.\n1.\tFollowing the decision of the consortium partner Lucerne Cantonal Police to leave the consortium due to the impossibility of having sites ready for installation of systems in line with their own project schedule, Swisscom and BKPNW offered to take the installation of the two systems originally proposed for LucPol.\n2.\tInitial on-field test sites in Turkey were at Four Seasons Hotel in Istanbul. However, due to the diminishing interest of the business management, the consortium decided to look for another partner. Turkcell, the largest GSM telecommunication company in Turkey, accepted to offer two sites to be utilized in FITUP project for a duration of one year each, without becoming member of the consortium.\n3.\tIn Turkey initially manufacturers prepared themselves for providing systems with compressed hydrogen cylinders to the hotel installation. However, due to the high cost of hydrogen logistics in Turkey, Turkcell did not see economic viability in that option and asked for a system with electrolyzer which at the end might offer a business case. The manufacturers accepted to change their original planning for the favour of producing the exact configuration demanded by Turkcell.\nLot 1 of fuel cell systems, consisting of 11 of 13 systems to be produced, were manufactured in due time according to data listed in Table 3:\n\nThe two missing fuel cell systems with electrolysers for Turkcell were manufactured and delivered with some months of delay also because of some complications arisen at the customs due to unprecedented nature of the shipment.\n\nThe complete list of produced systems is reported in Table 5.\n\nTask 2.2: System optimisation\nThis task refers to the optimization of the fuel cell systems once installed at user\u2019s site.\nThis work has been done by the manufacturers on systems installed at research centre facilities and for systems installed at final users\u2019 sites.\nWithin this task both manufacturers performed the system optimization at research centres and final users\u2018 sites once the systems has been installed.\nIt is important to underline that while the basic products are standard production routine, there were some aspects of RTD work that also play a role in this Work package. The power level and the necessary integration of an electrolyser in the application for WIND is new and required some RTD work prior to shipping them to the client site. The added site in Turkey created a similar situation for Future E, as the client there also requested on-site hydrogen generation via electrolyser due to the difficult topographic accessibility of the site. Furthermore, from the point of view of a manufacturer the use of their products by RTD Centers in benchmarking exercises also constitutes an RTD task.\n\nDeliverables\nThree deliverables were foreseen in this workpackage and fully achieved:\n\u2022\tD 2.1 Fuel cell systems for benchmark tests; 6 total systems.\n\u2022\tD 2.2 Fuel cell systems for field testing, lot 1; 11 total systems.\n\u2022\tD 2.3 Fuel cell systems for field testing, lot 2; 2 total systems for the sites in Turkey.\n\n2. WP3 \u2013 Installation\nWorkpackage 3, led by LUASA, deals with the installation of the 19 FC-UPS systems, the hydrogen supply infrastructure and the data acquisition. 13 systems have been installed as backup power sources for telecommunications companies and radio security network at selected end-user sites in Italy, Switzerland and Turkey. The other 6 systems have been installed at the research centres ICHET in Istanbul and JRC in the Netherlands for benchmark-testing according to a defined test protocol.\nTable 6 shows how the systems are distributed geographically and the partners in charge of the main tasks. All FC-UPS systems are provided by the two producers ElectroPS and FutureE. The supply of the hydrogen equipment for final users is in charge of the producers as well. The research centres are already equipped with a hydrogen supply infrastructure. The test and data acquisition equipment is provided and installed by the relative research centre which is in charge for conducting and monitoring the tests.\n\nIn the project firstly the nominal and maximum loads and power types of the individual end-user sites were identified and a suited FC-UPS system was agreed. Corresponding to the systems for end-user sites the technical specifications for the systems for benchmark testing were defined. Table 4 shows the basic technical data of the FC-UPS system at the different sites.\nWithin this WP four tasks have been identified and executed:\nTask 3.1 Site preparation\nFor the preparation process at end-user sites several steps had to be considered. The approach in the project was the following:\n\u2022\tIdentification of site requirements (site inspection, accessibility) \n\u2022\tEngineering of structural works and electrical integration (preparation of layout, \u2028electrical scheme, alarm and communication concept) \n\u2022\tStructural works (wall openings, concrete plates for placement of the cabinet) \n\u2022\tSubmission of authority approval if required.\nIn a first step the requirements of the individual sites were identified. A site- inspection was arranged at each site for the FC-UPS providers and the relative research centres which are in charge of testing. Technical requests were checked as well as the available space for the placement of the FC-UPS systems, the cooling system and the hydrogen supply equipment. Special attention had to be given to the accessibility of the sites for the delivery of the pressure cylinders. The decision on indoor or outdoor solution and hydrogen pressure cylinders or electrolysers was made according to the different local conditions. Furthermore it has to be clarified if an already existing backup system will remain on site. According to these requirements the site specification list was completed for each site. \u2028According to the decision of the FC-UPS type the engineering of structural works and electrical integration had to be done. An installation layout was made for each site to design the placement of the FC-UPS unit, the hydrogen supply system and the piping. Also an electrical scheme was prepared for the electrical integration of the components into the existing installation as well as an alarm and communication concept. The alarm concept includes hydrogen alarms and FC-UPS alarms which are to be added to the available structure of the corresponding end-user control system.\nThe end-users arranged the achievement of the structural works for the assembly of the FC-UPS enclosure, the appropriate cooling system and the placement of the hydrogen cabinet. These works consists mainly of the preparation of concrete plates for cabinet placement, of the preparation of wall openings for the air cooling system and for piping.\nInstallations with hydrogen have to follow specific standards and rules. For the field installations in Switzerland the approval of a local authority was requested. The systems with electrolyser technology for the sites in Italy and in Turkey don\u2019t need an approval by a local authority because the hydrogen storage volume is below a defined limit by local rules.\n\nTask 3.2 Installation of hydrogen infrastructure that complies with local regulations\nFor hydrogen supply two different systems are provided: hydrogen stored in pressure cylinders and hydrogen produced on site by electrolyser systems. Within the project the hydrogen supply equipment and the piping is supplied by the FC-UPS producers. This decision was made in order to offer a complete and for the end-user most comfortable solution.\nThe hydrogen supply equipment without electrolyser technology consists of the following components:\n\u2022\thydrogen cabinet\n\u2022\tpressure reducing and measuring devices\n\u2022\tsafety vents\u2028\n\u2022\tsolenoid valve\u2028\n\u2022\thydrogen sensor for indoor-installations (supplied by one manufacturer)\n\nHydrogen is provided in 50 Litre cylinders with 200 bar. One cylinder has a weight of around 63 kg and contains 8.9 Nm3 of hydrogen or 26.7 kWh of stored energy (lower heating value). In combination with FC technology one cylinder contains around 12 kWhel of stored electrical energy. The capacity of the hydrogen storage was designed according to the end-users requirements. Therefore the chosen cabinets may store 4 to 6 cylinders. For normal operation 3 respective 4 cylinders are connected in parallel. The others are kept in reserve in order to deliver hydrogen in case of the first cylinders have to be changed. This concept assures a replacement of the cylinders during the operation of the FC system.\nFor the replacement of the cylinders the accessibility to the sites is an important variable. Within the project there is a diversity of different kind of accesses by road, rural road, rack railway or elevator and stairs in a building. At 2 Polycom sites a 72 hours test will be carried out. The process of the cylinder replacement for this test scenario was checked in advance with the hydrogen provider. Due to steep and narrow roads the accessibility is restricted especially during winter time. The specifications of the hydrogen installations with pressure cylinders, the autonomy time and the accessibility of the different sites are summarized in table 7.\n\nThe 3 installed systems with electrolyser technology in Italy integrate an additional electrolyser module in the outdoor cabinet. At 2 sites the storage comprises 6 hydrogen cylinders with a volume of 50 Litre and at one site 10 cylinders. As hydrogen will be produced on-site the cylinders don\u2019t need to be changed. The specifications of the hydrogen installations with electrolyser technology and the expected autonomy times are summarized in table 8.\nIn Turkey the hydrogen storage is included in the complete system. No cylinders need to be changed as hydrogen will be produced on-site. The EPS system provides a cabinet with six 50 Litre hydrogen cylinders. FutureE stores hydrogen in two 1000 Litre tanks. \n\nThe hydrogen installation and piping has to comply with general standards and local rules. \nThe following European standards are to be considered:\n\u2022\tSN EN 62282-3-1 FC technologies. Part 3-1: Stat. FC power system - Safety, 2007 \n\u2022\tSN EN 62282-2 FC technologies. Part 2: FC modules, 2007 \n\u2022\tSN EN 62282-3-3 FC technologies. Part 3-3, Stat. FC power system - Installation, 2008 \n\u2022\tEC machinery directive \u2028\nAdditionally national standards and local terms of reference must be adopted or respected. \nAll installations were inspected by our project partner T\u00dcV S\u00dcD. Furthermore all Telecom sites needed an approval by a national inspection authority.\n\nTask 3.3 Installation of fuel cell systems \nA total number of 6 FC-UPS systems have been  installed at the R\u0026D centres ICHET and JRC for benchmark testing. Both suppliers provide 3 FC-UPS systems. ICHET will test 2 systems, one from each manufacturer, whereas JRC will test 4 systems, 2 from each manufacturer. All but one system are indoor systems and delivered to the R\u0026D centres. \nAll systems are rated 6 kW with nominal voltage of -48 VDC as shown in table 4. Both suppliers inspected the test facilities at the research centres in advance. An existing hydrogen supply infrastructure is available. Hydrogen is provided externally from a centralized hydrogen line which is connected to hydrogen gas cylinder bundles located outdoors. Additional structural works or the submission of an authority approval is not required. The testing equipment is supplied and installed by each R\u0026D centre and comprises common agreed components as described in deliverable D4.1. The measurement data will be uploaded directly from the measurement PC.\nPictures of the installations in the testing facilities are shown in figures 1 and 2.\n\nOut of a total number of 13 FC-UPS field installations there are 7 systems for telecommunications, 3 systems for radio security network and 3 systems are applied as backup for the cooling system of a Telecom provider in Italy. 5 of all systems are equipped with electrolyser technology.\nThe diversity of locations makes it possible to prove the functionality of the FC systems under different environmental conditions. The following locations may be pointed out:\n\u2022\tOne indoor-installation is at an altitude of 2215 m above sea level \n\u2022\tTwo outdoor-installations are at an altitude of around 800 m above sea level \n\u2022\tOne outdoor-installation is close to the entrance of a tunnel - increased emissions are expected in environmental air \n\u2022\tOne outdoor-installation is close to the sea \nThe FC-UPS systems including the cooling systems and hydrogen cabinets were sent in advance to the end-users. After the completion of structural works and site preparations the end-users organised the placement of the enclosures. At two sites the placement with a crane was necessary.\nBoth FC-UPS suppliers installed the systems at each site in collaboration with the users and the relative R\u0026D centre. The installation comprises the assembly of the cooling equipment, the electrical connection and the alarm configuration to the existing infrastructure.\nThe figures 3 and 4 show end-user sites in the field with outdoor systems, figure 4 additionally with electrolyser module.\n\nThe figures 5 and 6 show end-user sites in the field with indoor systems.\n\nEach installed unit undergoes a start-up procedure to ensure proper performance. The start-up procedure involves the control of the start-up time and the set-up of the voltage level at which the FC unit starts. During one start-up procedure it was realised that the nominal load is too low for a proper performance of the FC unit. During the testing period an additional load will be needed.\nThe commissioning of the systems involves the start-up procedure, the testing of the alarms and the training of the users.\n\nTask 3.4 Installation of testing data and data acquisition equipment \nThe testing equipment is supplied and installed by the relative R\u0026D centre which is in charge of testing. The procedure of grid failure simulations and the monitoring will be done remotely in collaboration with the control centres of the end-users. The remote control capability minimizes the necessity for onsite visits.\nThe components of the testing equipment are common agreed for benchmarking and field testing to compare the results. Main parts are the measurement PC, the signal conditioning board and devices for current and temperature measurement. \nThe integration of the components in the existing infrastructure, the placement of the parts and the work-sharing was agreed carefully with the end-users. For the installations in Switzerland Lucerne UASA is the R\u0026D centre in charge. For the installations in Italy and Turkey the R\u0026D centres EP and ICHET implement the testing equipment.\nFor the placement the existing space and the aspect of an easy removal after the project was important. At the Polycom sites the complete measurement equipment is placed in a separate rack, at the Telecom sites the equipment is installed on panels for the placement in existing racks. For the systems with electrolyser technology the measurement equipment is integrated in the FC rack.\nPreassembly and cabling was done at the R\u0026D centres, together with the preparation of electrical schemes for cabling. All panels were tested before the installation on site. \nMeasurement data will be acquired from the installed measurement devices and from the FC unit itself. For communication and data transfer a communication concept and the appropriate components had to be defined. The data will be transferred to the server of the R\u0026D centre respective the Telecom end-user will store the measurement data on its own server due to security reasons. During the start-up procedure trial runs were conducted to ensure that the equipment works properly.\n\nDeliverables\nTwo deliverables were foreseen in this workpackage and fully achieved:\n\u2022\tD 3.1 Installation and Commissioning report.\n\u2022\tD 3.2 Instllation Completion report for fuel cell systems \u2013 Lot 2\n\nMilestones\nMS3 System Start-up completed \nThe installation of the systems is one of the first defined milestones in the FITUP project. The works proceeded in an excellent collaboration of end-users, producers, research centres, certification body and project management. The systems at the research centres, all 8 systems with hydrogen supply by pressure cylinders in the field and 5 systems with electrolyser technology are installed successfully. \nDuring the installation process of the hydrogen infrastructure and the preparation of the security measures an uncertainty existed how to adopt the general security standards and local requirements for fuel cell applications. The involvement of the project partner T\u00dcV S\u00fcd and of a local inspection authority was important to gain confidence.\nThe following points have been identified:\n\u2022\tThe process of getting an approval by local authorities was less complicated in case a local provider was involved in the hydrogen installation. \n\u2022\tThe level of standardization may be checked to meet the needs for an effective production process on the one hand and to stay flexible for customer requirements on the other hand. \nAll fuel cell systems have been installed at both research centre and final user sites to be tested for two year with exception of systems in Turkey, where Turkcell, the largest GSM telecommunication company in Turkey, accepted to offer two sites to be utilized in FITUP project for a duration of one year each, without becoming member of the consortium.\n\n3. WP4 \u2013 Testing\nWorkpackage 4, led by EP and involving all partners: R\u0026D centres, FC systems manufactures and final users, with the only exception of UNITOV, deals with the testing activities at both lab and final user sites.\nIt is important to mention that following the shutdown of UNIDO-ICHET in December 2012 and rearrangement of the consortium and workplan accordingly, two systems that had been tested at ICHET for benchmarking were sent to FutureE and Environment Park. The results of the tests for the system at Future-E is however analyzed by LUASA.\nWithin this WP five tasks have been identified and executed:\n\nTask 4.1 Definition of test architecture\nA common test architecture has been defined  for both benchmarking and test on-field. Nevertheless some differences come out in different locations, due to system characteristics and installation issues. \nIn the benchmarking tests the controlled test variables (test inputs) have been defined as follows:\n\u2022\texternal grid power availability (controlled through a controlled power switch)\n\u2022\tload applied to the UPS systems\n\u2022\tenvironment temperature (only during climatic chamber tests)\nThe resulting measured variables (test outputs) are:\n\u2022\tvoltage and current at fuel cell system terminals\n\u2022\tvoltage and current at start-up batteries (or ultracapacitors) terminals\n\u2022\tvoltage and current at electronic load terminals.\nThus benchmark test system is composed by the following parts:\n\u2022\tan industrial pc used to control the tests and collect the data through an acquisition board, equipped with necessary signal conditioning devices\n\u2022\ta temperature sensor used to monitor the environment temperature\n\u2022\tthree couples of cables that carry the voltage signals to the acquisition board\n\u2022\tthree shunts used to measure the currents \n\u2022\tan electronic load that absorb the power produced by the UPS\n\u2022\tan ac\/dc converter used to power the load using AC power, before the grid failure simulations\n\u2022\ta controlled switch that breaks the connection between the AC\/DC converter and the grid\n\u2022\tan optional hydrogen sensor, used to detect gas leakage in the test environment.\naccording to the setup shown in figure 7.\n\nIn the on-field tests the main target is to confirm the functionality, reliability and good performance of the system, therefore grid failure simulations are performed in all the on-field installations of the project. \nThe controlled test variables (test inputs) during on-field tests of systems equipped with compressed hydrogen cylinders are:\n\u2022\texternal grid power availability (controlled through a controlled power switch).\nThe resulting measured variables (test outputs) are:\n\u2022\tvoltage and current at fuel cell system terminals\n\u2022\tvoltage and current at start-up batteries (or ultracapacitors) terminals\n\u2022\tvoltage and current at electronic load terminals.\nThe test system is composed by the same components of benchmark test system with exception of the load that of course is present on-site.\nThe setup of test systems for sites with fuel cell systems equipped with H2 cylinders is shown in figure 8.\n\nThe precise installation procedure of the test equipment will vary from site to site, depending on the characteristics of the place, but some basic rules have been defined in order to ensure the correct working of the system.\nThe hydrogen sensor must be placed in the higher point of the system room in case of indoor installations (outdoor installations don\u2019t need this device).\nThe ambient temperature sensor should be placed as close to the fuel cell as possible, in order to have a correct information about the temperature close to the UPS.\nThe shunts, used to measure the current at fuel cell and batteries terminals, should be installed as close as possible to these devices. The shunt that measures the current going to the load should be instead placed immediately after the insertion of the backup systems on the DC bus, i.e. as far as possible from the load, in such a way that the ohmic losses on the bus are taken into account as loads. It is also necessary to place the shunts in a way that the heat produced by the shunts (around 10 W) can be dissipated.\nThe voltage measurement points should be placed before shunts connections, excluding in this way the voltage drop on the shunts from the measurement.\nThe measurement cables should be shielded and as short as possible, in order to reduce electrical noise.\nThe fuel cell system and start-up batteries (or ultracapacitors) must be installed and connected to the required supplies (air, hydrogen, \u2026) according to manufacturer indications.\n\nRegarding tests to be performed on systems equipped with electrolyser, power absorbed by the electrolyser has been defined as additional variable to be measured. Accordingly a power meter that measures the power consumption of the electrolyser is added to be installed as close as possible to the electrolyser according to the setup shown in figure 9.\n\nTask 4.2 Development of test protocol\nA test protocol has been defined to be followed in both laboratory benchmark experiments and on-field tests, in locations defined by final users.\nThe main purpose of the tests is to demonstrate that the fuel cell UPS systems satisfy the following objectives, stated in the project:\n\u2022\treliability higher than 95%\n\u2022\tdurability higher than 1500 hours and 1000 cycles (real-time or extrapolated)\n\u2022\tresponse time smaller than 5ms\nThe reliability will be statistically verified at the end of the whole test campaign. Final users also specified that their usual reliability requirements are higher than 99%, and they expect that the tested systems will meet them.\nResponse time will be controlled at each system start-up.\nThe requirements in terms of durability will be instead completely checked only for 4 systems, two for each manufacturer involved in the project. These systems will be operated for more than 1500 hours, and will carry on more than 1000 on-off cycles. The data collected from these tests will be used to predict the aging of the other systems. The long-time tests will be operated in laboratory, due to the logistic complexity of the hydrogen tanks replacement in real-world applications.\nIn addition to the mere verification of project objectives, during the tests additional data will be collected in order to investigate system performances and obtain useful information for manufacturers and final users.\nThe described protocol could also be used as a standard performance test for fuel cell UPSs, both in laboratory and in real world applications.\nAs a starting point for the test protocol development activities, in order to understand how to test the UPS units in a realistic way, the characteristics of the electrical grid failures, especially in terms of duration and frequency have been studied. Existent reports coming from previous research projects and industrial tests concerning test procedures of this kind of systems were taken into account as well. \nGrid stability is improving in Europe, however there are still some outages. Major weather problems and unexpected consequences of repair and maintenance works can affect even generally stable and highly developed grids.\nApart from very short failures (on which complete data are not available), it is possible to classify the outages in the following way:\n\u2022\tshort term (less than 1 hour)\n40-60% of cases on L2 and L3 networks, happen also on L1 grid. Average duration of 15\u2019-20\u2019\n\u2022\tmedium term (1 hour)\n20-30% of cases on all grid levels\n\u2022\tlong term (2 hours)\n20-30% of cases on all networks, less frequent than medium term ones\n\u2022\tcatastrophic (more than 24 hours)\npossible once a year in all grids at least regionally.\nThe obtained results have been used as a basis for the development of a mix of grid failure simulations that represent the reality. \nThe grid failure simulations have been divided in three main groups, each one characterized by a different duration and representing a statistical class of failures that actually happen in electrical grids:\n\u2022\tshort term grid failures (A type), duration of 15\u2019\n\u2022\tmedium and long term grid failures (B type),  duration of 240\u2019 (4 hours)\n\u2022\tcatastrophic grid failures (C type), duration of 4320\u2019 (72 hours).\nB and C type simulations have a larger duration compared to the actual grid failures of the same class. The duration of B failures has been fixed in order to create test procedures respecting the given number of on-off cycles and hours of operation. C simulations satisfy instead a particular demand coming from some end users, that would like to check if the systems can match TETRA applications requirements.\nHowever, since the above said durations are larger than real world ones, the resulting tests are more stressing for the systems than usual functioning. As a consequence, if the systems will be able to withstand the programmed tests, they will prove to be capable of working in harder conditions than normal operation in Europe.\nDuring laboratory tests, each kind of grid failure simulation will be performed at different power levels (50%, 75% and 100% of total system power). This will not be done in on-field tests: in fact, in real-world applications it is not possible to choose the load applied to the systems.\n\nMoreover, two different start-up conditions will be employed:\n\u2022\twarm start up (1 type), duration of the off time before the cycle 1\u2019\n\u2022\tcold start up (2 type), duration of the off time before the cycle 60\u2019 (minimum)\nThe characteristics of the simulations and their frequency are indicated in the following table.\n\nFive test procedures were defined, taking care of different test objectives, locations and system characteristics:\n\n1.\tLONG-TIME DURABILITY BENCHMARK test (BENCH-LTD)\n2.\tADDITIONAL BENCHMARK tests (BENCH-ADD)\n3.\tON-FIELD test for systems with COMPRESSED H2 CYLINDERS (OF-CH2)\n4.\tON-FIELD test for TETRA systems with COMPRESSED H2 CYLINDERS (OF-TET)\n5.\tON-FIELD test for systems equipped with ELECTROLYSER (OF-ELS)\n\nEvery procedure has been constructed combining the cycles listed in table 10. The precise description can be found in deliverable 4.1.\n\nThe assignment of the test procedure to each installed system is showed.\n\nDuring the testing period, because of some technical drawbacks occurred during benchmarking tests at JRC,  some revisions were introduced in tests protocol. According to the Amendment to the DOW of the 19th of March 2013 Deliverable 4.2 Revised test protocol (M29) was therefore introduced.\n\nTask 4.3 Benchmarking\nA total of 6 fuel cell UPS systems have been manufactured for benchmark tests in R\u0026D centres. \nBenchmark tests were carried out at JRC and ICHET in the first part of the project. Following the shutdown of ICHET and rearrangement of the consortium and workplan accordingly, two systems that had been tested at ICHET were sent to FutureE and Environment Park. \nIdentical systems have been manufactured and sent to the R\u0026D centres in order to provide the reference functional operating information in a controlled environment. All the system used for Benchmarking test are fed with compressed hydrogen, and not by electrolysers.\nJRC have also completed specific tests in the climate chamber for both cold start and tropical conditions as defined in the testing protocols. \nA target number of start-up shut-down cycles and hours of operation was defined at the beginning of the project as requested by the call:\n\u2022\t1000 Start-up \/ Shut-down cycles\n\u2022\t1500 hours of operation\nAt the end of the testing period more than 4600 hours of test were completed, with over 4000 cycles and a production of 16 MWh of electric energy.\nThe table 11 summarises the progress of the test done according to the protocols defined in the task 4.2 and in the Deliverable D4.2:\nDetailed description of benchmarking activities is reported in deliverable D4.3. \nDetailed test history of each fuel cell system is reported and test results are described with regards to the following parameters:\n\u2022\tReliability (target \u003E95% as requested by the call).\nReliability has been investigated considering the main causes of the failures:\n-\tFuel cell system malfunction, due to the degradation of the fuel cell (voltage degradation) or to the BOP components malfunction;\n-\tH2 equipment, due to the lack of H2 feeding; \n-\tMeasurement equipment, due to the malfunction of internal or external equipment;\n-\tMaintenance, due to an improper maintenance of the machine;\n-\tInstallation, due to an improper installation of external equipment.\n\u2022\tHydrogen consumption (performed in each research centre) that provides information on system efficiency.\n\u2022\tFuel cell performance degradation in order to estimate lifetime and replacement time of the stack\n\u2022\tStart-up time (response time \u003C5ms as requested by the call).  \nMain conclusions can be summarized as follows: \nAll the systems reported 23 failures over 4045 power interruptions for a reliability value of 99.4%. Laboratory environment has a very high reliability in term of hydrogen infrastructure, and this has allowed performing so many hours of test without interruption.\nData-logging hardware has worked properly in laboratory environment, with a reliability of 99.9% with 3 failures over more than 4000 test. No interferences or failures arose from the artificial blackout provoked by the system.\nEfficiency was calculated with the electrical energy produced by the system and the amount of hydrogen energy used. The efficiencies of the fuel cell without the power of the batteries are between 30% and 50%.\nHydrogen consumption tests have identified an important information for the end users who is basically interested in:\n\u2022\tAvailable energy (in kWh)\n\u2022\tResidual backup time\nAs a summary result from all consumption tests done 100 grams per kWh is the worst case of all the systems at maximum power rate, this value can be safely used by the telecom operator in order to define the storage capacity to be installed in the site.\nDegradation effects are not clearly comparable between systems coming from the two suppliers, as the two hardware architectures are radically different. The average voltage drop during 1,000 h of runtime is around 4%. At the end of the testing period the fuel cell system delivered still the maximum power of 6 kW.\nThe start-up time, the time it takes for the system to recover the 50% and the 75% of the load, that is considered a more interesting parameter with respect to response time, results to be in a time ranging from 20-30 seconds (\u003E 98%).\n\nTask 4.4: Data acquisition\nAll sites were equipped with the same data-logging hardware and software. Every experiment generates multiple files at different sampling rate in order to understand what happens during the interruption event (1,000 Hz) and during the rest of the test at lower speed (default 1 Hz). Grid restore is logged at high frequency (1,000 Hz default) in order to capture transients. \nEach test is recorded with the following files:\n\u2022\tSTART files are logged at high speed (default 1,000 Hz)\n\u2022\tREG files are logged at a nominal 1 Hz frequency\n\u2022\tSTOP files are logged at high speed (default 1,000 Hz)\n\u2022\tEPS or Fut-E files are logged at the same speed of the REG files\nStart and Stop files are useful to understand if the response and start-up time of the system is correct according to the specifications. A specific software for a quick visualization was created to check these information during the test or during the final data analysis.\nIn order to quickly analyse the resulting data a visualization tool was implemented. Using this tool in few clicks it is possible to check what happened to the system. \nIn order to reduce the data a specific pre-processing tool was implemented using labview. The pre-processor is designed to analyse every file of each test to create a single summary record in which all the most interesting information are stored. Every summary line store the following information, extracted by the START, STOP and REG file:\n\n1.\tMachine ID\n2.\tDate\n3.\tTime of the interruption\n4.\tCause of the interruption (S for software G for grid falure, which means a real blackout)\n5.\tFail Type (A1, A2, B1\u2026)\n6.\tAverage Current during the interruption from the shunts (I_BAT, I_FC, I_LOAD)\n7.\tAverage Voltages during the interruption\n8.\tMinimun and maximum voltage  during the interruption\n9.\tAverage power (calculated by a point by point integral on the data files)\n10.\tIntegral of the energy procuded by the system\n11.\tAverage temperature during the test\n12.\tStart-up time to reach 50% and 75% of the load\n13.\tHours and Cycles counter\n14.\tLast value of current and voltage before the end of the test (blackout end)\nThe result of the pre-processor is an ASCII table (CSV file) that can be read directly from excel to draw summary charts.\nFull description of data acquisition methodology is reported in both deliverable D4.3 Report on results of benchmarking and deliverable D5.1 Report on field test results.\n\nTask 4.5: Field testing at end-user sites\n13 market ready systems have been installed at real world sites of telecommunications base stations and police communications stations across Europe. Status of the testing activities at the end of the project can be seen in Table 12 in comparison to the expected numbers found in the project\u2019s Description of Work. Test cycles have been implemented in each site according to a specific test procedure developed for different type of applications as resumed in Table 10. \nEach test procedure is made of a number of different types of cycles, as elaborated in deliverable 4.1 Development of Test Protocol and confirmed in deliverable 4.2 Revised Test Protocol. \n\nA total of 6,352 cycles have been tested in these 13 systems corresponding to 1,941 hours of testing.\nIn Switzerland a total of 8 systems were installed in the field, whereof 5 systems were tested at Swiss telecom operator Swisscom and three systems at POLYCOM sites for the national security network. For all systems hydrogen were supplied in 200 bar pressure cylinders with a volume of 50 liter. At the end of the on-field testing the target was completely fulfilled with a total of 4,082 cycles and 1,054 grid-off hours. About 1.9 MWh of energy were produced during grid failure simulations at real life installations in the field. The tests were performed in accordance with the developed testing procedures. One system for the security network was tested for nearly 72 hours to meet the requirements of the end user. \n\nIn Italy a total of three systems were installed and tested in the on-field site of telecom operator WIND. The 3 systems installed in Italy are equipped with an electrolyser and a booster for hydrogen compression up to 150 bar. During the on-field test 590 hour of testing was completed for a total of 1,645 cycles consisting three different type of cycles: A1, A2 and B2.\nIn Turkey two systems were installed at the telecom operator Turkcell\u2019s sites in Bursa. Total of 625 cycles corresponding to 298 hours of tests. Turkcell joined the project after it started as an external partner. Previously tests in Turkey would take place in some residential building. Both systems in Turkey were equipped with electrolyzers one with 150 bar and the other 30 bar of hydrogen storage depending on the manufacturer.\nResults coming from analysis of all collected data are described in WP5. \n\nDeliverables\nThree deliverables were foreseen in this workpackage and fully achieved:\n\u2022\tD 4.1 Definition of test protocol.\n\u2022\tD 3.2 Revised test protocol\n\u2022\tD 4.3 Report on result of benchmarking\n\nMilestones\nMS4 Benchmarking completed\nMS5 Field tests completed \n4. WP5 \u2013 Analysis\nFollowing the shutdown of ICHET and rearrangement of the consortium, the WP was lead by BILGI UNI, involving all R\u0026D centres and the FC system manufacturers.\nActivities in this work package can be grouped as analysis of the data of the laboratory tests, analysis of the data of on-field tests, in charge of IBU (task 5.1) and life cycle analysis, in charge of UNITOV (task 5.2). LCA results will be presented in the following paragraph related to the socio-economic impact of the project results. \n\nTask 5.1: Analysis of test data\nData analysis have been implemented with respect to the guidelines developed by the work package partners in order to sustain highest level of harmony possible for analysis of both field test data and benchmarking data. Strict cooperation between WP4 and WP5 activities and partners has been performed.\n\nStarting from the status of the testing activities at the end of the project and main results in terms of reliability and response time summarized in Table 12, the test results have been analysed focusing on the three distinct goal of the project:\n\u2022\tReliability greater than 95%\n\u2022\tResponse time less than 5 ms\n\u2022\tNo considerable performance deterioration after the tests.\n1. Reliability of the fuel cell systems as given in Table 12 are defined by the failures that caused the systems not respond to a grid failure. When calculating the reliability numbers of failures are divided to the total number of test cycles to give a percentage measure. In this analysis this terminology is used to give a general understanding of all the systems tested in the project. However, there are different meanings for different types of failures. On the other hand, there are some cases that the systems are down due to maintenance but these are not considered as failures because it was taken as granted that the system would not respond to a grid failure in this condition. \nEvents are divided into 5 categories:\n\u2022\tFuel Cells System Failure\n\u2022\tHydrogen Production \/ Infrastructure\n\u2022\tMaintenance\n\u2022\tMeasurement Equipment (FITUP data monitoring hardware)\n\u2022\tInstallation issues\nOf these categories, only those related with fuel cell system and electrolyzer are considered as failures and count towards reliability calculation in Table 12.\nA total of 6,352 cycles have been tested in these 13 systems corresponding to 1,941 hours of testing. The systems responded to 6,310 of these grid failure simulations successfully making the average reliability of 99.3%, which is well above the project goals. Individual system reliability has differed from 97% to 100%, which assures each of tested systems has surpassed the projected goals individually. \nWhen the failures are analysed for each system, it is found that many of the failures are due to minor parts in the system like pressure regulator or valves. These can be avoided easily by using alternative products and optimizing the products. Indeed some parts in some systems have been replaced with new items as part of the manufacturers optimizing their product line in the course of the project with the insights acquired from the test results.\nFailures in the Italian and Turkish installations are mainly concentrated around hydrogen generation equipment, which can be avoided again by upgrading the available products with the feedback from the project. It should be also noted that electrolyzer was not included in the original project proposal.\nOn-field installations in Italy and Turkey with an average reliability of 98.9% have shown that the intensive usage of the electrolyzer to reach the target of interruptions and cycles of the project has created some maintenance problems to the electrolyzers.\nThose targets of hours and cycles were defined on the basis of the residual test time: a too optimistic assumption was done in term of the availability of hydrogen produced by the electrolysers. Too much intensive use of the electrolysers has caused more maintenance operations that expected (water tank fillings), corresponding to a lower availability of the overall system.\nOn-field installations in Switzerland with compressed hydrogen cylinders reached with more than 4,000 cycles and over 1,000 hours of operation time the fully target of testing. Average reliability of the systems tested in Swiss sites has been found to be 99.4%, which is slightly higher than systems in Italy and Turkey that are equipped with electrolyzers.\nHowever, it was understood that there is not a single best solution that applies all. System architecture should be optimized with respect to the demands of the customer. At some sites systems with H2 generation may be preferred while in some cases hydrogen delivery may make more sense.  \nAlthough test results agree well with the project goals, there may be stricter goals such that some end users of telecom and security network demand a reliability of more than 99.9%. The project showed that the quality of the peripheral parts is crucial for the reliability of the fuel cell systems and these goals can be reached by the optimization of the products.\nWith one test period of nearly 72 hours the system was tested according to the end user requirement for the security network. The fuel cell delivered the demanded power without any problems during this time and without maintenance personnel on site. This is a significant benefit of fuel cells in comparison with other backup solutions and shows the viability of the systems.\n2. The response time for all systems was 0 ms due to the fact that the start-up batteries were always attached to the bus bar. In case of a grid failure they are able to deliver the demanded power without interruption until the fuel cell starts up. With this system architecture the objective of the project to show a response time less than 5 ms is completely achieved.\n3. All the systems are proven to provide the same rated power at the end of the tests which hints that there is not a considerable deterioration in the system performance.\n4. In addition hydrogen consumption has been evaluated by measuring and logging the pressure in the hydrogen bottles for the field installations in Switzerland. With the pressure data the overall consumption over the complete testing period per kilowatt-hour was calculated. The results for all installations are shown Figure 10. \nThe dark blue bars show the hydrogen consumption during the operation time of the fuel cell system. The light blue bars show the complete hydrogen consumption comprising the consumption according to the number of cylinder changes. Due to the remaining gas volume before replacement and due to leakages the latter consumption is higher.\nThe system POLYCOM03 sticks out of the others with a higher consumption. This is due to the fact that the load was very low and therefore the working point of the fuel cell system was unfavourable. Secondly, there was an undiscovered leakage quite close after a cylinder replacement. A more detailed consumption analysis was done for each individual site and reported in deliverable D5.1.\nBased on these pressures measurement data and the overall produced energy during the testing period the efficiency of the systems were calculated . Taking all hydrogen deliveries per site into account the efficiencies are between 20% and 30%. The efficiencies calculated with the hydrogen consumption of the real operating time differ between 33% and almost 50%. The lowest value is due to the fact that the fuel cell system was in an unfavourable operation mode with low load. The average efficiency over all sites is 41%. The results are shown in Figure 11. \n\nWith the consumed amount of hydrogen and the overall produced energy during the testing period costs in Euro per kWh are calculated. The mean costs per kWh for the FC real operating time over all sites were 5 Euro\/kWh. Including the costs for the complete volume of the delivered gas the mean costs are around 6 Euro\/kWh. In consideration of the complete hydrogen infrastructure with transport and rental fees the costs differ from 11 to 15 Euro\/kWh (without POLYCOM03). A summary of the costs is shown in figure 12. \n\nThe mean efficiency of 41% shows that the technology is closing in market demands. \nAlso all results show that technical viability of fuel cell technology is proven.\nHowever, as better described in the following paragraph, the investment costs are still high in comparison with batteries and diesel generators and there is still a feeling of uncertainty towards fuel cell and hydrogen technology on the part of the end users. A wide spread of the technology in Europe will help to reduce these constraints. Further funding will be necessary to reach this goal.\n\nDeliverables\nTwo deliverables were foreseen in this workpackage (task 5.1)and fully achieved:\n\u2022\tD 5.1 Report on test results.\n\u2022\tD 5.2 Public Report on test results\n\n\nPotential Impact:\nAs above stated, one of the main objectives of the FITUP project is to demonstrate the economic and environmental maturity of back-up and UPS power systems based on fuel cell technology.\nAccordingly, several activities have been performed within WP5, WP6 and WP7 related to life cycle analysis, certification issues, dissemination and non-technical barrier to market deployment, respectively. All related deliverables are public.\n \n1. WP5 \u2013 task 5.2 Life Cycle Analysis\nThe main goal of this study is to compare fuel cell backup power systems with standard backup technologies as battery and diesel. This comparison is made with regard to environmental aspects. In order to guarantee conformance to the ISO 14040 and 14044 standards on Life Cycle, the LCA report was carried out following the International Reference Life Cycle Data System (ILCD) Handbook and the HC-FC Guide \u201cGuidance Document for performing LCAs on Fuel Cells and H2 Technologies\u201d. In particular, the study is in line with ILCD Handbook guidelines with respect to the following aspects:\n\u2022\tData quality: relates to completeness, representativeness (technological, geographical and time-related), precision\/uncertainty, methodological appropriateness and consistency;\n\u2022\tMethod: relates to the appropriateness of the Life Cycle Inventory modelling and other method provisions, and the consistency of their use;\n\u2022\tNomenclature: relates to correctness and consistency of nomenclature which has been used (appropriate naming of flows and processes, consistent use of ILCD reference elementary flows, use of units etc.) and terminology (use of technical terms);\n\u2022\tReview: relates to the appropriateness and correctness of the review type, review methods and documentation. This includes ensuring that the methods used to carry out the LCA are consistent with ILCD guidance document, and are scientifically and technically valid; \n\u2022\tDocumentation: relates to several topics, that is documentation extent (appropriate coverage of what is reported), form of documentation (selection of the applicable forms of reporting and documentation), documentation format (selection and correct use of the data set format or report template, and review documentation requirements);\nA TCO analysis has been included as comparison criteria.\nThe Life Cycle Analysis performed on Fuel Cell backup systems allow to assess the environmental impact of system assembly and its usage. In particular, results of the analysis show that the manufacturing of both Balance of Plant and Stack are important. Within the Stack assembly, attention should be taken to improve efficiency of production processes and raw material utilization for Electrodes and Bipolar Plates.\nFor the analysed type of application, that is backup systems used for few hours in a year, system life-cycle is in fact more influenced by FC UPS manufacturing rather than its usage. This effect is emphasized when an ever more sporadic use of the system is taken into account (like in Italy and Switzerland scenarios). \nAs a consequence, in order to enhance environmental performance, system design and manufacturing process optimization should be pursued by manufacturers. Alternatively, by improving system efficiency, the size of components could be reduced on equal nominal power of the FC, thus obtaining a positive effect.\nThe comparison of competing technologies (FC, Battery and Diesel UPS) in three different scenarios confirms that the FC backup system is an environmental friendly solution, especially when the required operating hours decrease and, as a consequence, the stack lifetime can be sensibly extended. In fact, considering the majority of the environmental categories analysed, this technology proved to be the best choice for all scenarios when external supply of hydrogen and nominal power of 6kW is concerned. The Abiotic Depletion is the only category in which the FC shows a very high impact if compared to Diesel and Battery UPS. This effect is mainly due to the production of hydrogen. However, by carrying out a normalization analysis on European and Worldwide data, it was possible to state that Abiotic Depletion represents an important category but its normalised environmental load is minor if compared to other categories such as Marine Aquatic Ecotoxicity.\nFollowing objectives of the FITUP project, the effect of different hydrogen supply and nominal power of the system were tested. Alkaline electrolysis was analysed and its negative influence on environmental performance of FC UPS was pointed out. However, even considering an electrical energy mix characterised by a high percentage of fossil fuels for energy production, FC technology remains the most environmental friendly backup systems even using on-site production of hydrogen. Moreover, the negative effect of electrolysis, mainly due to the lower efficiency of the electrolysis process if compared to gas reforming, can be reduced by using photovoltaic energy.\nThe economic analysis, carried out using the Total Cost of Ownership Criteria, showed that the FC UPS has a lower cost than both Diesel and Battery UPSs on a horizon of 12 years, which is the expected lifetime of the system for the intended application. The break-even point for the selected utilization scenario (90 operating hours) is between the seventh (Diesel) and eighth (Battery with 2 hours of autonomy) year. According to the analysis, in order to improve FC UPS marketability, effort should be made to reduce the purchase cost, stating the low relative importance of OPEX. \nThen, increasing manufacturing efficiency by reducing the quantity of precious metals in FC stack, optimising stack design and improving production process performance seem key aspects, to be taken into account by manufacturers developing FC UPS.\n\nDeliverables\nOne public deliverable was foreseen in this task and fully achieved:\n\u2022\tD 5.3 Report on Life Cycle Analysis\n\n\n2. WP 6 - Certification\n\nThe main objectives of this workpackage, lead by EPS but supported strongly by TUEV Sued who has specific expertise in the field of RCS, are:\n\u2212\tResearch and comparison of existing requirements for:\n\u2022\tthe gas supply system for above named Fuel Cell Systems;\n\u2022\tthe installation and use of above named Fuel Cell Systems and valid in selected EU countries.\n\u2212\tPreparation of a uniform systematic certification and installation procedure for Fuel Cell Systems for portable generators, backup and UPS power systems.\n\nIt is important to underline that the starting basis of the work has been the existing EU standards on fuel cell systems already published including other findings from previous and on-going projects, such as Hyperprojects, Harmonhy, and Hysafe. \n\nAccording to the declared objectives within this WP three tasks have been identified and executed:\n\nTask 6.1: Comparison of existing requirements for the gas supply systems (hydrogen cylinder)\nTask 6.2: Comparison of existing requirements for installation and use of Fuel Cell Systems\nGeneral existing requirements for manufacturing, installation and operation of Fuel Cell Systems and pressure vessels and cylinders have been pointed out and fully reported in the public deliverable D 6.1.\nIn general there are mandatory regulations and standards for the design, construction and operation of fuel cell systems, pressure vessels and cylinders.\nIn Europe these are the EC regulations with the CE-marking for the manufacturing and EC regulations with their national implementations for the operation.\nNormally the requirements for the fuel cell systems are laid down mainly in following EC directives for the manufacturing:\no\t97\/23\/EC Pressure Equipment Directive\no\t2006\/42\/EC Machinery Directive\no\tDirective 94\/9\/EC on the approximation of the laws of the Member States concerning equipment and protective systems intended for use in potentially explosive atmospheres (valid until 20\/04\/2016);\no\tDirective 2014\/34\/EU on the harmonisation of the laws of the Member States relating to equipment and protective systems intended for use in potentially explosive atmospheres (recast);\no\tDirective 2006\/95\/EC on the harmonization of the laws of Member States relating to electrical equipment designed for use within certain voltage limits (valid until 20\/04\/2016);\no\tDirective 2014\/35\/EU on the harmonization of the laws of Member States relating to the making available on the market of electrical equipment designed for use within certain voltage limits (recast);\no\tDirective 2004\/108\/EC on the approximation of the laws of the Member States relating to electromagnetic compatibility and repealing Directive 89\/336\/EEC (valid until 20\/04\/2016);\no\tDirective 2014\/30\/EU on the harmonisation of the laws of the Member States relating to electromagnetic compatibility (recast);\nAll components installed in a fuel cell system in Europe shall be marked with their applicable CE-markings to show the compliance with the relevant EC directive.\nAnd in the following EC directives the requirements for the operation are laid down:\no\t2009\/104\/EC Directive for safety requirements for the use of work equipment\no\t2003\/105\/EC Seveso II Directive\no\t1999\/92\/EC Directive on minimum requirements improving the safety and health protection of workers potentially at risk from explosive atmospheres\no\t98\/24\/EC Directive for the protection of health and safety of workers from chemicals.\nThese EC directives are implement in national regulation and laws in all member states of the EU to fulfill the requirements for safety on work and safe operation.\nComplete information for selected EU countries: Italy, France, Germany, Norway, Switzerland Austria and Turkey, with special reference to the completed installations have been collected and fully reported in the public deliverable D6.1.\n\nTask 6.3: Proposal for a uniform systematic certification procedure for Fuel Cell Systems\n\nThe certification of fuel cell systems shall be generally be based on following procedure:\n\nThe targets of this certification procedure are:\n-\tAcceptance by user and public;\n-\tAt least the same safety level as for conventional technology.\n\nThe certification process consists in two constituent parts:\n1.\t\u201cProcedural Safety\u201d - concept \n2.\t\u201cHandling\u201d \u2013 technical testing\nFor every Fuel Cell Power System (portable or stationary) and every Fuel Cell Module, the manufacturer has to develop a general safety strategy. Therefore, the first important topic for the whole certification is the development of an adequate safety concept. The strategy to develop the safety concept shall consist in following three steps:\n-\tEvaluation of relevant protection devices\nBasis: FMEA, HAZOP, etc.\n-\tEvaluation of qualitative requirements\nsafety related components, e.g. IEC 61508, IEC 61511 (reliability, SIL)\n-\tRealization of the safety concept \nquality verification and documentation\nAfter developing the conceptual design of the fuel cell system, it has to be determined which European Directives are applicable for the system, e.g.:\n-\t2014\/35\/EU, 2006\/95\/EC (until 20\/04\/2016): Low Voltage\n-\t2014\/34\/EU, 94\/9\/EC (until 20\/04\/2016): ATEX\n-\t2014\/30\/EU, 2004\/108\/EC (until 20\/04\/2016): Electromagnetic Compatibility\n-\t97\/23\/EC: Pressure Equipment (PED)\n-\t2010\/35\/EU: Transportable Pressure Equipment (TPED)\n-\t2006\/42\/EC: Machinery\nIn addition to the European Directives, there are harmonized standards that shall be applied to fulfil the requirements regarding a safe operation of fuel cell systems.\n\nRegarding the installation of the UPS power systems, it his highly recommended to identify the local authorities, which are responsible for the permit of operation, in an early stage of the project. The responsible local authorities will be able to provide information about special national or local requirements regarding the installation of fuel cell systems, electrolyser systems and gas supply systems, as storage tanks, cylinders and bundles of cylinders.\n\nFor each UPS power system, the manufacturer has to provide the information necessary for safe installation and operation. \nThe information must be provided in the form of technical documents such as drawings, diagrams, charts, tables and instructions, and these shall be on suitable data medium and language. In standard EN 62282-3-100:2012, chapter 7.4, following different types of manuals are described.\n\nOne of the most important lessons learned during the project, is the need of detailed instruction for the change of cylinders. The people who change the cylinders are mostly not familiar with the UPS power systems. Therefore, it is very important to provide detailed information about the steps to follow during a change of cylinders. This information shall be part of the installation manual, the maintenance manual or the operating manual.\n\nDeliverables\n\nOne public deliverable was foreseen in this task and fully achieved:\n\n\u2022\tD 6.1 Proposal for a uniform certification procedure for Fuel Cell Systems\n\n\n2. WP 7 - Dissemination and Exploitation\n\nOne of the primary goals of Early Market project is to achieve success stories and to have as much of the public know about it as possible. This is why the dissemination activities within the FITUP project have been considered crucial.\nIn addition the identification and the addressing of non-technical barriers to deployment of fuel cell systems as backup power solutions represent another fundamental activity providing clear information on potential impact of the projet.\n\nThus within this WP two tasks have been identified and executed:\n\nTask 7.1 Dissemination\n\nThe FITUP Website www.fitup-project.eu has been established in the first year by UNIDO-ICHET, posting all information on the project, updates on events, meetings and conduction of the project activities. Following the shutdown of ICHET and rearrangement of the consortium, the dissemination task has been taken over by BILGI UNI. New website address had to be changed to www.fitup.engr.bilgi.edu.tr because .eu could not be registered from Turkey which is the host country of Bilgi University. Website has been updated following the activities in the course of the project. \n\nDuring the project period partners have presented the project results at different level:\n\n- Potentially interested industries: the project results have been presented in international conferences targeting backup power\/UPS industry:\n\u2022\tGSMA 2011 in Barcelona : poster presentation by EPS\n\u2022\tGSMA 2012 in Barcelona: poster presentation by EPS\n\u2022\tGSMA 2013 in Barcelona: poster presentation by EPS\n\u2022\tIntelec 2013 in Hamburg: FITUP results have been presented in Intelec 2013, Hamburg 13-17 October 2013, in a dedicated tutorial \u201cFuel cells fundamentals, their fuels, their testing and advantages and disadvantages and their state of development for backup power solutions\u201d held in a common presentation by FutureE, LUASA and EPS\n- A dedicated workshop \u201cA Fuel Cell Backup Power for Telecommunications Workshop\u201d has been held in Istanbul last 24 April 2014, addressed to related industry especially those from telecommunications. Companies based in Turkey have been informed on an invitation basis while the workshop was for all the interested partners from other locations. In the workshop results from FCPoweredRBS project have been presented as well.\n\nThe flyer of the event is shown here below.\n\n- Hydrogen community: \n\u2022\t2011 Hannover Fair: poster presentation by EPS\n\u2022\t2013 Hannover Fair: presentation of the project within the technical forum by EPS \n\u2022\t2014 Hannover Fair: presentation of the project within the technical forum by EPS\n\u2022\t2011 FCH Review Days: presentation of the project by EPS\n\u2022\t2012 FCH Review Days: presentation of the project by EPS\n\u2022\t2013 FCH Review Days: presentation of the project by EPS\n\u2022\t4th European PEMFC and H2 Forum 2013 in Lucerne, Switzerland presentation of the project by LUASA\n\u2022\tEuropean Fuel Cell Forum Conference 2013, 11-13 December 2013, Rome, Italy, presentation of the project by EPS and BILGI UNI.\n\n- General public:\n\u2022\tEuropean Parliament, Brussels, 5 October 2011: project presentation by EPS \n\u2022\tWorkshop on Small Scale Fuel Cell Technology for Residential and Industrial Applications in Gebze 5 May 2013 by BILGI UNI;\n\u2022\tTubitak\u2019s Horizon 2020 workshop in Istanbul in November 2013 by BILGI UNI;\n\u2022\tA site visit at the installation in Lucerne was offered to EFCF attendees, 27 June 2012. About 40 researchers participated in the visit \n\n- Publications:\n\u2022\tFITUP \u2013 Fuel Cell Field Test Demonstration of Economic and Environmental Viability for Portable Generators, Backup and UPS Power System Applications, Ulrike Trachte, Peter Sollberger Beat Wellig, Proceedings of 4th European PEFC and H2 Forum, July 2013, Switzerland.\n\nTask 7.2: Non-technical barriers to deployment\nThe objective of this task is to provide an assessment report of all those barriers to deployment that are not specific to the technical performance of the products demonstrated.\nSuch barriers were originally conceptualized to be mainly in the framework conditions under which the products compete with both incumbent technologies which in the case of UPS\/back-up power systems are primarily lead-acid battery banks and those additionally equipped with a generator set for energy supply lasting longer than the battery bank capacity, and alternative technologies that may come up during the project.\nThe most critical part was expected to be differences in the way the fuel cell technology was treated in the RCS (regulations, codes \u0026 standards) sector as hydrogen safety represents a new subject for the operators and zoning\/permitting authorities. Some of the additional effort necessary to achieve a safe operating status was expected to be a perceived source of resistance.\nWhile this part of the work is addressed by WP6, the experience of the project demonstrated that operating permits could be achieved at all sites, although sometimes requiring extra effort, which resulted in delayed system start-ups and higher installation cost.\nThe FITUP Consortium thus decided to look at the non-technical barriers to deployment in a broader sense. As these barriers could also be seen as the main variables in determining the \u201cproximity-to-commercialization\u201d and a measurement methodology had been suggested in another FCH-JU project and also been implemented in the technology monitoring and assessment tool the FCH-JU program office has started to use, the FITUP consortium decided to utilize the Expert Judgement Mapping routines of the TEMONAS solution with the assistance of one of its architects, Mr. Herbert Wancura.\nThe methodology used in the EJM is a computer supported Delphi method of Expert Consensus. Generally it is designed as a two round system, where the expert pool is enabled to select their judgments to each of the parameters.\nThe second round then presents them with the range of answers and judgments in a statistical format of MIN, MAX, AVG. Based on this information the experts are then selecting their new values, which may also be the same as in the first round of judgments. \nExtreme values are recorded but require the addition of an explanation comment. The rationale is that in the typical application of the EJM a set of issues arise:\n\u2022\tSmall quantity of responses due to relatively small sample size prohibits truncation due to its major effects on the results\n\u2022\tThe timing of the EJM is typically one where major uncertainty still persists. Scientific literature [11] recommends the more detailed analysis of \u201cthings that don\u2019t fit\u201d as it could contain \u201cweak signals\u201d that could be important.\nUnder typical circumstances the second round would again be run computer supported and would yield a new and typically, more narrow range. Given the special situation of the FITUP project where anonymity of judgment was not so critical, it was decided to proceed towards an open second round format in a workshop which also enabled discussion and an agreement on a single consensus value. This may deviate from the typical Delphi methodology, but was seen as acceptable as it replicates the method of achieving expert consensus in the ex-ante peer reviews for EC-cofinanced projects.\nThis workshop session was held as part of the FITUP project meeting in Munich on April 12, 2014. Mr. Wancura, who co-developed the methodology in the TEMONAS project, acted as facilitator and as rapporteur.\nInformation collected is fully reported in the deliverable D7.2. \nConclusions and recommendations can be summarized as follows.\nOverall the experts from the FITUP Consortium have a rather positive outlook regarding their technology vis-\u00e0-vis its main competition as can be seen from the following positioning graph.\n\nThey expect the main incumbent technologies to see markets of equal attractivity coming down from higher levels \u2013 mostly volumes based \u2013 due to increasing customer requirements while their offer will continue to develop positive in terms of relative competitive advantage.\nHowever, while this may be correct in the overall sector, the sub-segment of telecom radio base stations (RBS) may see massive overall changing of the value chain, with telecom operators increasingly looking for models enabling them to reduce CAPEX as they are faced with margin pressures due to regulatory and competitive activity. One path seems to be \u201cbuild and operate\u201d models for RBS from the suppliers of RBS equipment, where the customer would switch from the end user to an intermediary which is likely to pay close attention to their break-even point which in turn strongly depends on initial capital outlays.\nIn terms of recommendations regarding the removal or reduction of non-technical barriers to deployment the following items should be considered:\n1\tWhile the European Union clearly has no competence in taxation matters the significant structural difference to the US is clearly a disadvantage to European industry from the sector. If this cannot be changed alternative forms of demand stimulation need to be developed; some initial phases possibly coming in new structuring of demonstration programs under FCH-JU 2.0.\n2\tRegulation is still very regionally fragmented and needs harmonization. Ideally this would be in the format of a directive including clear references to international standards. Alternatively, there are various guidelines from FCH-JU and earlier programmes and a proposal from WP6 on a harmonized procedure. It may be a good initiative to create a task force with the Member States Representatives Group to actually build a recommended harmonized procedure which is then legislated as necessary in a similar fashion by each member state.\n3\tIn terms of standardization we recommend a CSA supporting the industry consisting mainly of SME\u2019s in developing application specific standards. This could be coordinated by the JRC.\n\n\nDeliverables\n\nTwo  public deliverables were foreseen in this task and fully achieved:\n\u2022\tD 7.1 Project website\n\u2022\tD 7.2 Report on non-technical barriers to deployment\n\nList of Websites:\nProject website: http:\/\/fitup.engr.bilgi.edu.tr\/\nProject coordinator: Ilaria Rosso, Electro Power Systems S.p.A. ilaria.rosso@electropowersystems.com.\n\n","reportTypeDescription":"P-CSA-NoE Final Report","identifiers":{"reportId":"1245685"},"sourceUpdateDate":"2017-02-21 10:57:00","contentCreationDate":"2015-08-10 17:53:12","contentUpdateDate":"2015-08-10 17:55:59","lastUpdateDate":"2025-10-16 08:48:09","archivedDate":"2024-06-23 00:00:00","relations":{"associations":[{"availableLanguages":"de,en,es,fr,it,pl","rcn":"91078","id":"91078-fuel-cells-empower-grids","title":"Fuel cells empower grids","teaser":"Cumbersome banks of batteries and diesel generators provide the vast majority of emergency power. EU-funded researchers demonstrated that fuel cell powered systems are a better back-up solution for irregular disruptions in power grids.","contentUpdateDate":"2016-03-04 14:09:53","archivedDate":"2024-06-10 00:00:00","relations":{"categories":[{"language":"en","availableLanguages":"de,en,es,fr,it,pl","code":"ener","title":"Energy","displayCode":"\/Energy","attributes":{"classification":"applicationDomain","type":"isApplicableIn"}},{"language":"en","availableLanguages":"de,en,es,fr,it,pl","code":"brief","title":"Result in Brief","description":"Article: Classic and enhanced","displayCode":"\/Result in Brief","attributes":{"classification":"collection","type":"belongsTo"}},{"language":"en","availableLanguages":"de,en,es,fr,it,pl","code":"editorial","title":"CORDIS Editorial","description":"Written by CORDIS","displayCode":"\/CORDIS Editorial","attributes":{"classification":"source","type":"isProvidedBy"}}],"associations":[{"language":"en","availableLanguages":"de,en,es,fr,it,pl,any","uri":"\/docs\/results\/images\/2016-02\/169311.jpg","mimetype":"image\/jpeg","size":"0","copyright":"\u00a9 Thinkstock","contenttype":"webItem","attributes":{"represents":"article","source":"editorial","type":"relatedImage"}}]},"contenttype":"article","attributes":{"source":"editorial","type":"relatedArticle"}},{"availableLanguages":"en","rcn":"3116975","legalName":"ELECTRO POWER SYSTEMS","address":{"country":"IT"},"contenttype":"organization","attributes":{"source":"sesam","type":"relatedOrganization"}},{"availableLanguages":"en","rcn":"97957","id":"256766","acronym":"FITUP","title":"Fuel cell field test demonstration of economic and environmental viability for portable generators, backup and UPS power system applications","archivedDate":"2024-06-18 00:00:00","relations":{"categories":[{"language":"en","availableLanguages":"de,en,es,fr,it,pl","code":"project","title":"Project","description":"Project factsheets","displayCode":"\/Project","attributes":{"classification":"collection","type":"belongsTo"}},{"language":"en","availableLanguages":"de,en,es,fr,it,pl","code":"\/25\/73\/30020\/455","title":"telecommunications","displayCode":"\/engineering and technology\/electrical engineering, electronic engineering, information engineering\/information engineering\/telecommunications","attributes":{"classification":"euroSciVoc","type":"isInFieldOfScience"}},{"language":"en","availableLanguages":"de,en,es,fr,it,pl","code":"\/25\/67\/425\/1173","title":"fuel cells","displayCode":"\/engineering and technology\/environmental engineering\/energy and fuels\/fuel cells","attributes":{"classification":"euroSciVoc","type":"isInFieldOfScience"}},{"language":"en","availableLanguages":"en","code":"JTI-CP-FCH","title":"Joint Technology Initiatives -  Collaborative Project (FCH)","displayCode":"\/Joint Technology Initiatives -  Collaborative Project (FCH)","attributes":{"classification":"projectFundingSchemeCategory","type":"relatedProjectFundingSchemeCategory"}},{"language":"en","availableLanguages":"de,en,es,fr,it,pl","code":"corda","title":"CORDA","description":"RTD research data warehouse","displayCode":"\/CORDA","attributes":{"classification":"source","type":"isProvidedBy"}}],"associations":[{"availableLanguages":"de,en,es,fr,it,pl","rcn":"870","id":"FP7-JTI","code":"FP7-JTI","frameworkProgramme":"FP7","pga":"FP7-JTI","title":"Specific Programme \u0022Cooperation\u0022: Joint Technology Initiatives","shortTitle":"Joint Technology Initiatives","parent":{"rcn":"846\/1401\/837","code":"FP7-COOPERATION\/EC\/FP7"},"archivedDate":"2024-06-12 00:00:00","relations":{"categories":[{"language":"en","availableLanguages":"de,en,es,fr,it,pl","code":"legalbasis","title":"Legal Basis","description":"Programme: Legal basis for research funding","displayCode":"\/Legal Basis","attributes":{"classification":"collection","type":"belongsTo"}},{"language":"en","availableLanguages":"de,en,es,fr,it,pl","code":"editorial","title":"CORDIS Editorial","description":"Written by CORDIS","displayCode":"\/CORDIS Editorial","attributes":{"classification":"source","type":"isProvidedBy"}}]},"contenttype":"programme","attributes":{"source":"corda","type":"relatedLegalBasis"}},{"availableLanguages":"en","rcn":"13328","id":"FP7_SP1-JTI-FCH.2009.4.2","code":"SP1-JTI-FCH.2009.4.2","frameworkProgramme":"FP7","title":"Portable generators, backup and UPS power systems","parent":{"rcn":"11952\/11937\/11928\/870\/846\/1401\/837","code":"SP1-JTI-FCH-4\/SP1-JTI-FCH\/SP1-JTI\/FP7-JTI\/FP7-COOPERATION\/EC\/FP7"},"archivedDate":"2024-06-14 00:00:00","relations":{"categories":[{"language":"en","availableLanguages":"de,en,es,fr,it,pl","code":"topic","title":"Topic","description":"Programme: Part of the Commission work programme implementing legal basis","displayCode":"\/Topic","attributes":{"classification":"collection","type":"belongsTo"}},{"language":"en","availableLanguages":"de,en,es,fr,it,pl","code":"editorial","title":"CORDIS Editorial","description":"Written by CORDIS","displayCode":"\/CORDIS Editorial","attributes":{"classification":"source","type":"isProvidedBy"}}]},"contenttype":"programme","attributes":{"source":"corda","type":"relatedTopic"}}]},"contenttype":"project","attributes":{"source":"sesam","type":"relatedProject"}}],"categories":[{"language":"en","availableLanguages":"de,en,es,fr,it,pl","code":"pubsum","title":"Report Summary","description":"Result: Publishable summary (FP7 SESAM) and Summary for publication (H2020 SyGMa)","displayCode":"\/Report Summary","attributes":{"classification":"collection","type":"belongsTo"}},{"language":"en","availableLanguages":"de,en,es,fr,it,pl","code":"sesam","title":"SESAM","description":"RTD FP7 reporting system (including FP6 Marie Curie)","displayCode":"\/SESAM","attributes":{"classification":"source","type":"isProvidedBy"}}],"regions":[{"name":"Italy","rcn":"309758504","nutsCode":"IT","euCode":"IT","isoCode":"IT","attributes":{"source":"sesam","type":"relatedRegion"}}]},"modelVersion":"132","icaVersion":"20.0.0-48f81e07"}