SOLAR ASSISTED ABSORPTION OR MOTOR DRIVEN COMPRESSOR HEAT PUMPS WITH EARTH SEASONAL STORAGE

Objectif



IN THIS PROJECT CARRIED OUT BY THE UNIVERSITY OF PADOVA, ITALY AN ABSORPTION HEAT PUMP (NH3/H2O) OF 25 KW HEAT OUTPUT WAS CONNECTED WITH A SIMPLE 100 M2 ENERGY ROOF AND A VERTICAL HEAT EXCHANGER CONSISTING OF 16 CONCENTRIC TUBES OF 15 M LONG. BOTH THE ENERGY ROOF AND THE HEAT EXCHANGER CAN BE USED AS A HEAT SOURCE FOR THE HEAT PUMP. MOREOVER THE ENERGY ROOF CAN BE USED TO REGENERATE THE HEAT IN THE SOIL BY MEANS OF THE HEAT EXCHANGER. THE INSTALLATION WAS CONSTRUCTED FOR THE HEATING OF A 1 080 M3 TWO STOREY BUILDING.

THE ENERGY CONVERSION EFFICIENCY OF THE ENERGY ROOF WAS 10 - 15 % AND DURING THE SUMMER AROUND 80 KWH WAS DELIVERED PER DAY. TEMPERATURES IN THE SOIL WERE MEASURED NEAR THE TUBES AT DEPTHS OF 1,5, 8 AND 15 M. THE HIGHEST TEMPERATURE DURING REGENERATION AT 15 M WAS 16 DEGREES C. IN SPITE OF THE REGENERATION DURING THE SUMMER SOME TUBES HAD LOWER TEMPERATURE AFTER ONE YEAR OF OPERATION. THE EFFICIENCY OF THE ABSORPTION HEAT PUMP WAS LOW; THE PER VALUE WAS 0,8. THIS IS NOT MUCH HIGHER THAN FOR A CONVENTIONAL BOILER. THE PROJECT HAS NOT YET FINISHED AND DATA ON COST AND PAYBACK TIME ARE NOT YET AVAILABLE.

Thème(s)

Data not available

Appel à propositions

Data not available

Régime de financement

Data not available

Coordinateur

Metalux SpA
Contribution de l’UE
Aucune donnée
Adresse
Via Triestina 74
30024 Musile di Piave
Italie

Voir sur la carte

Coût total
Aucune donnée