Objectif THIS CONTRACT IS A SHORT FOLLOW-UP CONTRACT OF WORK CARRIED OUT IN THE FIRST PROGRAMME. A 330 KW (THERMAL) ICE DRIVEN HEAT PUMP WAS DEVELOPED WHICH PRODUCES STEAM AT 110 DEGREES C; WASTE HEAT AT 80 DEGREES C SERVES AS A HEAT SOURCE. THE COP VALUE IS 1.5. PROBLEMS HAVE BEEN ENCOUNTERED WITH STEAM FLOW MEASUREMENT AND COMPRESSOR OIL/REFRIGERANT MIXING. IN THE FRAMEWORK OF THE CEC DEMONSTRATION PROGRAMME THE ECONOMIC FEASIBILITY OF THIS HEAT PUMP IS NOW BEING INVESTIGATED. IN THE FRAMEWORK OF THE CEC DEMONSTRATION PROGRAMME THE ECONOMIC FEASIBILITY OF THIS HEAT PUMP IN CHEMICAL INDUSTRY IS NOW BEING INVESTIGATED. Programme(s) PRE-ENNONUC 2C - Energy research and development programme (EEC), 1979-1983 Thème(s) Data not available Appel à propositions Data not available Régime de financement Data not available Coordinateur NEI International Research and Development Company Ltd Contribution de l’UE Aucune donnée Adresse Fossway NE6 2YD Newcastle upon Tyne Royaume-Uni Voir sur la carte Coût total Aucune donnée