VENTILATED SOLAR WINDOW-HEAT PUMP SYSTEM, FOR BUILDING HEATING

Objective

The project aims to demonstrate the commercial potential of a so-called "Solar Ventilated Window" (VSV) as a transparent energy saving prefabricated component. This element is applied in the restructuration of a old school building to reduce the heating load. The use of the VSV is complemented with a air-water heat pump as main heating system for the building.

The project is carried out during the restructuration of army barrack of the 19th centrury which was already converted to a school building in the years 1950.
The new heating system is composed of 2 subsystems. The first one is a series of solar ventilated windows on the south side of the building. The window consists of 2 glasses with an airspace of 7 cm in which venetian blinds are mounted and which can be manipulated and oriented manually. The curved side of the blinds are white (for reflection in summer) and black at the other side (for heat captation in winter). The air flux through the airspace is by thermosyphonic circulation through grilled openings at the bottom and top of the frames.
These openings are controlled manually according to the needs. Supplemental advantage f these windows concern the comfort, as daylighting and noise reduction.
The second subsystem, which will complement the heating needs consists of 2 heat pumps (one air-water and one water-water). It is intended to use the extracted air from the class room and/or ambient air as heat input for the heat pumps.
Some technical data of the building are :
- total useful surface (on 3 floors) : 3376 m2
- total windows surface : 993 m2 (246 m2 south)
- wall thickness : 50 cm
- climate : mediterraneal-dry
- useful surface concerned by the solar system : 1272 m2
The following designed energy consumptions are calculated :
1) the present heating needs : 535 mWh/year
2) with ventilated solar windows (VSV) : 382 mWh/year
3) 2) + heat recuperation system by heat pumps : 108 mWh/year
4) 3) + double glazing on N,W,E : 68 mWh/year
The ventilated solar windows permit a saving of 38 mWh/year as insulation and 114 mWh/year as solar gain. The heat pumps supply 56 mWh/year, obtained by the air extraction from the classrooms.

Fields of science (EuroSciVoc)

CORDIS classifies projects with EuroSciVoc, a multilingual taxonomy of fields of science, through a semi-automatic process based on NLP techniques. See: The European Science Vocabulary.

This project has not yet been classified with EuroSciVoc.
Be the first one to suggest relevant scientific fields and help us improve our classification service

You need to log in or register to use this function

Programme(s)

Multi-annual funding programmes that define the EU’s priorities for research and innovation.

Topic(s)

Calls for proposals are divided into topics. A topic defines a specific subject or area for which applicants can submit proposals. The description of a topic comprises its specific scope and the expected impact of the funded project.

Call for proposal

Procedure for inviting applicants to submit project proposals, with the aim of receiving EU funding.

Data not available

Funding Scheme

Funding scheme (or “Type of Action”) inside a programme with common features. It specifies: the scope of what is funded; the reimbursement rate; specific evaluation criteria to qualify for funding; and the use of simplified forms of costs like lump sums.

DEM - Demonstration contracts

Coordinator

ECOTECNIA SOCIEDAD COOPERATIVA CATALANA LTD
EU contribution
No data
Address
C/AMISTAD 23, 1ER
08005 Barcelona
Spain

See on map

Total cost

The total costs incurred by this organisation to participate in the project, including direct and indirect costs. This amount is a subset of the overall project budget.

No data