PV ELECTRIFICATION OF DISPENSARIES IN GUADELOUPE

Objective

To install solar powered vaccine refrigerators and lighting at 40 sites on the island of Guadeloupe (total power 9.216 kWp). The most important aspect is the reliability of the power supply: the cold chain for the vaccines must not be interrupted.

33 sites have a 200 litre refrigerator, 6 panels (48 W each), battery 195 Ah, 24 V.
7 sites have a 140 litre refrigerator, 4 panels (48 W each), battery 135 Ah, 24 V.
Nr. subsystems : 40
Power subsys. : 33 x 288 Wp + 7 x 192 Wp
Total power : 10.8 kWp
Backup : grid
Nr. of modules : 226
Module descript. : PHOTOWATT BPX 47500, polycrystalline, bi-glass
Connection : two in series
Support : on the roofs, on AI support, 25 deg. from horizonta
l Max. pwr trcker : none
Chrg controler : special design by APEX, with alarms. Permits low water consumption of batteries, 3 years maintenance intervals.
Battery : OLDHAM MTS 100 lead acid, open with recombination.
Capacity :
Batt. (Ah) : 135
Batt. (kWh) : 3.2
Inverter : none
Load descript. : refrigerators RSA, 24 V dc powered
Monitoring: not foreseen