LIGHTHOUSE (SAPIENZA) POWERED BY PV AND WIND GENERATORS

Objectif

To demonstrate the reliable operation of a combined PV and wind generator to power a flashing beacon lighthouse in Greece. The existing system with a revolving oil lamp, which operates using counter-weights that are raised by hand is replaced by a long range flashing beacon consisting of halogen lamps each rated at 43 W.
The long term aim is that the system should be able to operate unmanned.
The pv power supply has operated in a satisfactory mode from November 1987 to November 1988, when, probably due to lightning stroke, the electronic components were destroyed. Repair has been made, along with improvement of the overvoltage protection. Since then the PV-lighthouse system works very well and has a high safety margin for permanent availability.
The unit energy cost is evaluated to be 16.9 ECU/kWh for the demonstration project and 7.0 ECU/kWh for a replication. DIESEL generation costs at such a site are of the order of 2.4 ECU/kWh.
1. INTRODUCTION
The project demonstrates a novel flashing beacon for use in lighthouses powered by PV. The approach reduces running costs both by saving fuel and by eliminating the need for personnel on site. The old oil lamps require manual winding every 1.5 hours, and the lighthouse is located 96 m above sea level in an inaccessible location. Three people are continuously in attendance to operate the existing system with a total of 6 persons working in shifts.
2. TECHNOLOGY
The new lamp system, type DSL3 is supplied by Pintsch-Bamag is of rotary type, flashing, reaches 23 nautical miles and consumes 1.3 kWh per day at an operating voltage of 10.7 V.
The PV system (1300 Wp) comprises 10 Siemens modules SM144-18 wired in 5 strings of 2 modules each. (One sub-array has 3 strings, the other one 2 strings.)
The 2 m diameter wind generator, rated at 1000 W in a wind of 13,2 m/s, also contributes via an inverter to the power requirements of the system. Each PV array is connected to thebattery via a charge controller, type LR45-24EK of Siemens Solar with two stages of load management.
The battery consists of a VARTA solar battery rated at 24V/2000 Ah giving 48 kWh of storage, allowing security of power for 36 days without sun.
The DSL3 halogen lamp gets its power at 10.7 V through three DC/DC converters.
3. MONITORING
A telemetry system, powered by PV array and battery, transmits the climatic and system performance data to a central station. It does also call by telephone automatically in case of an emergency. The data are also stored on site on magnetic tape for later analysis. The format is in accordance with JRC Ispra Monitoring Guidelines. Monitoring data are available from April 89 to May 1991.

Champ scientifique (EuroSciVoc)

CORDIS classe les projets avec EuroSciVoc, une taxonomie multilingue des domaines scientifiques, grâce à un processus semi-automatique basé sur des techniques TLN. Voir: Le vocabulaire scientifique européen.

Ce projet n'a pas encore été classé par EuroSciVoc.
Proposez les domaines scientifiques qui vous semblent les plus pertinents et aidez-nous à améliorer notre service de classification.

Vous devez vous identifier ou vous inscrire pour utiliser cette fonction

Programme(s)

Programmes de financement pluriannuels qui définissent les priorités de l’UE en matière de recherche et d’innovation.

Thème(s)

Les appels à propositions sont divisés en thèmes. Un thème définit un sujet ou un domaine spécifique dans le cadre duquel les candidats peuvent soumettre des propositions. La description d’un thème comprend sa portée spécifique et l’impact attendu du projet financé.

Appel à propositions

Procédure par laquelle les candidats sont invités à soumettre des propositions de projet en vue de bénéficier d’un financement de l’UE.

Données non disponibles

Régime de financement

Régime de financement (ou «type d’action») à l’intérieur d’un programme présentant des caractéristiques communes. Le régime de financement précise le champ d’application de ce qui est financé, le taux de remboursement, les critères d’évaluation spécifiques pour bénéficier du financement et les formes simplifiées de couverture des coûts, telles que les montants forfaitaires.

DEM - Demonstration contracts

Coordinateur

PUBLIC POWER CORPORATION (PPC)
Contribution de l’UE
Aucune donnée
Adresse
HEP DEV. DEPT 56-58 AGISIALOU STR.
10436 Athens
Grèce

Voir sur la carte

Coût total

Les coûts totaux encourus par l’organisation concernée pour participer au projet, y compris les coûts directs et indirects. Ce montant est un sous-ensemble du budget global du projet.